Meter Configuration
This chapter covers configuring the SDM630MCT-RC meter via the front LCD panel.
Entering Setup Mode
- Press and hold the E (Enter) button for 3 seconds
- The display shows the password prompt:
CodE 0000
- Use the ↑/↓ buttons to enter password: 1000 (default)
- Press E to confirm
- The first setup menu item appears
System Type Selection
| Setting |
Options |
Default |
| System type |
1P2W, 3P3W, 3P4W |
3P4W |
Navigate to Sys and select the wiring type matching your installation. Most 3-phase installations use 3P4W (3-phase 4-wire with neutral).
CT Ratio Configuration
Critical: The CT ratio MUST match the installed Rogowski coil rated current.
| Register |
Parameter |
Range |
Default |
| 40063 |
CT1 ratio |
1–2000 |
1 |
| 40063 |
CT2 ratio |
1–2000 |
1 |
| 40063 |
CT3 ratio |
1–2000 |
1 |
Setting CT Ratio via LCD
- In setup mode, navigate to
SEt → Ct1
- Use ↑/↓ to set the rated current of your ESCT-RC coil
- Press E to confirm
- Repeat for
Ct2 and Ct3

Common CT Ratio Settings
| Coil Model |
Rated Current |
CT Ratio Value |
| ESCT-RC80 |
1000A |
1000 |
| ESCT-RC100 |
2000A |
2000 |
| ESCT-RC150 |
5000A |
2000* |
*Note: Maximum CT ratio setting is 2000. For coils rated above 2000A, set the ratio to the maximum and apply scaling in software/MQTT.
| Register |
Parameter |
Range |
Default |
| 40065 |
PT ratio |
1–4000 |
1 |
Set to 1 for direct connection (no voltage transformer).
Communication Settings
Baud Rate
| Register |
Options |
Default |
| 40069 |
2400, 4800, 9600, 19200, 38400 |
9600 |
Modbus Address
| Register |
Range |
Default |
| 40071 |
1–247 |
1 |
Set a unique address for each meter on the same RS485 bus.
Parity
| Register |
Options |
Default |
| 40073 |
EVEN, ODD, NONE |
EVEN |
Pulse Output Configuration
| Register |
Parameter |
Default |
| 40079 |
Pulse output 1 mode |
Import active energy |
| 40081 |
Pulse output 2 mode |
Import reactive energy |
| 40083 |
Pulse width |
60ms |
Display Settings
Demand Integration Time (DIT)
| Register |
Options |
Default |
| 40085 |
1, 5, 8, 10, 15, 20, 30, 60 (minutes) |
15 |
Backlit Timeout
| Register |
Range |
Default |
| 40089 |
0–255 (minutes, 0=always on) |
5 |
Password Change
| Register |
Parameter |
Default |
| 40091 |
Setup password |
1000 |
Security recommendation: Change the default password (1000) to prevent unauthorized configuration changes.
Saving and Exiting
After all changes:
- Press and hold E for 3 seconds, or navigate through all menu items
- Changes are saved automatically
- The meter restarts with new settings
Configuration Quick Reference
| Parameter |
Register |
Default |
Recommended for RS-EMON3P |
| System type |
— |
3P4W |
Match installation |
| CT ratio (per phase) |
40063 |
1 |
Match ESCT-RC model |
| PT ratio |
40065 |
1 |
1 (direct) |
| Baud rate |
40069 |
9600 |
9600 |
| Modbus address |
40071 |
1 |
Unique per meter |
| Parity |
40073 |
EVEN |
EVEN |
| Password |
40091 |
1000 |
Change from default |