Meter Configuration

This chapter covers configuring the SDM630MCT-RC meter via the front LCD panel.

Entering Setup Mode

  1. Press and hold the E (Enter) button for 3 seconds
  2. The display shows the password prompt: CodE 0000
  3. Use the ↑/↓ buttons to enter password: 1000 (default)
  4. Press E to confirm
  5. The first setup menu item appears

System Type Selection

Setting Options Default
System type 1P2W, 3P3W, 3P4W 3P4W

Navigate to Sys and select the wiring type matching your installation. Most 3-phase installations use 3P4W (3-phase 4-wire with neutral).

CT Ratio Configuration

Critical: The CT ratio MUST match the installed Rogowski coil rated current.

Register Parameter Range Default
40063 CT1 ratio 1–2000 1
40063 CT2 ratio 1–2000 1
40063 CT3 ratio 1–2000 1

Setting CT Ratio via LCD

  1. In setup mode, navigate to SEtCt1
  2. Use ↑/↓ to set the rated current of your ESCT-RC coil
  3. Press E to confirm
  4. Repeat for Ct2 and Ct3

LCD Display CT Setup

Common CT Ratio Settings

Coil Model Rated Current CT Ratio Value
ESCT-RC80 1000A 1000
ESCT-RC100 2000A 2000
ESCT-RC150 5000A 2000*

*Note: Maximum CT ratio setting is 2000. For coils rated above 2000A, set the ratio to the maximum and apply scaling in software/MQTT.

PT Ratio (Voltage Transformer)

Register Parameter Range Default
40065 PT ratio 1–4000 1

Set to 1 for direct connection (no voltage transformer).

Communication Settings

Baud Rate

Register Options Default
40069 2400, 4800, 9600, 19200, 38400 9600

Modbus Address

Register Range Default
40071 1–247 1

Set a unique address for each meter on the same RS485 bus.

Parity

Register Options Default
40073 EVEN, ODD, NONE EVEN

Pulse Output Configuration

Register Parameter Default
40079 Pulse output 1 mode Import active energy
40081 Pulse output 2 mode Import reactive energy
40083 Pulse width 60ms

Display Settings

Demand Integration Time (DIT)

Register Options Default
40085 1, 5, 8, 10, 15, 20, 30, 60 (minutes) 15

Backlit Timeout

Register Range Default
40089 0–255 (minutes, 0=always on) 5

Password Change

Register Parameter Default
40091 Setup password 1000

Security recommendation: Change the default password (1000) to prevent unauthorized configuration changes.

Saving and Exiting

After all changes:

  1. Press and hold E for 3 seconds, or navigate through all menu items
  2. Changes are saved automatically
  3. The meter restarts with new settings

Configuration Quick Reference

Parameter Register Default Recommended for RS-EMON3P
System type 3P4W Match installation
CT ratio (per phase) 40063 1 Match ESCT-RC model
PT ratio 40065 1 1 (direct)
Baud rate 40069 9600 9600
Modbus address 40071 1 Unique per meter
Parity 40073 EVEN EVEN
Password 40091 1000 Change from default