Skip to content

Technical Specifications

This chapter provides the complete technical specification sheet for the SDM630MCT-RC, derived from the Eastron SDM630MCT datasheets.

Electrical Specifications

Parameter Value
System types 1P2W, 3P3W, 3P4W (default)
Rated voltage 3×230/400V AC (50/60Hz)
Operating voltage range 80–120% Un
Rogowski coil input 85mV/kA (SDM630MCT-RC)
Starting current 0.1% Ib
Frequency 50/60Hz ±10%
Power consumption ≤2W / 10VA
Auxiliary power 85–277V AC, 50/60Hz

Accuracy

Parameter Accuracy
Voltage 1.0% of reading
Current 1.0% of reading
Frequency 0.2% of reading
Power factor 1.0% of reading
Active energy Class 1 (IEC 62053-21)
Reactive energy Class 2 (IEC 62053-23)

Physical

Parameter Value
Dimensions 94.5 × 72 × 65 mm
Mounting DIN rail (35mm)
Display Backlit LCD
Protection IP51 (front panel)
Weight ~300g

Outputs

  • 2× pulse outputs (active + reactive energy), opto-isolated
  • 1× RS485 Modbus RTU port

Communication

Parameter Value
Protocol Modbus RTU
Baud rates 2400, 4800, 9600 (default), 19200, 38400
Address range 1–247 (default: 1)
Parity EVEN (default), ODD, NONE
Data format 8-bit, IEEE 754 float

Compliance

  • IEC 62053-21 (Class 1 active energy)
  • IEC 62053-23 (Class 2 reactive energy)
  • MID 2014/32/EU
  • CE marked
  • Measurement category: CAT III 300V

Operating Conditions

Parameter Range
Operating temperature -25°C to +55°C
Storage temperature -40°C to +70°C
Humidity ≤95% RH (non-condensing)

Ordering Variants

Model Input Type Output
SDM630MCT-RC 85mV/kA (Rogowski) Modbus + Pulse
SDM630MCT-MV 333mV (CT) Modbus + Pulse
SDM630MCT-0.33 333mV (CT) Modbus
SDM630MCT-1A 1A (CT) Modbus + Pulse
SDM630MCT-5A 5A (CT) Modbus + Pulse