DANGER — Electric Shock Risk

This product operates at voltages that can be lethal. Installation and maintenance must be performed by qualified electricians only.

  • Category III (CAT III) measurement category applies — suitable for distribution-level installations.
  • Disconnect all power before opening the enclosure or making any wiring changes.
  • Lock out / tag out (LOTO) procedures must be followed during installation and maintenance.
  • Verify absence of voltage with a rated voltage detector before touching any terminals.
  • Never operate the equipment with the enclosure open or covers removed.

WARNING — Rogowski Coil Installation

  • Ensure Rogowski coils are correctly oriented (arrow pointing toward load) before energizing the circuit.
  • Do not exceed the rated current for the selected Rogowski coil model.
  • Secure all cable connections before powering on — loose connections can cause arcing.
  • Ensure the coil fully encircles the conductor without gaps in the closure.

WARNING — RS485 Communication

  • Use twisted-pair cable for RS485 connections.
  • Install a 120-ohm termination resistor at each end of the bus for runs exceeding 10 meters.
  • Maximum RS485 bus length: 1200 meters.
  • Maximum number of nodes on a single bus: 32 devices.

Compliance

This product complies with:

  • IEC 62053-21 — Electricity metering equipment (AC)
  • MID 2014/32/EU — Measuring Instruments Directive
  • CE — European Conformity marking
  • CAT III 300V — Measurement category rating